DIN5510-2电线电缆成束燃烧测试-DIN EN 50266-2-4标准
EN 50266-2-4:2001: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Category C
EN 50266-2-4:2001: 着火条件下电缆的通用试验方法-多根成束垂直火焰燃烧-第2-5部分-类型C
EN 50266-2-4 together with BS EN 50266-1, EN 50266-2-1, EN 50266-2-2, EN 50266-2-3 and EN 50266-2-5, it supersedes BS 4066-3:1994 which is withdrawn
DIN 50266-2-4 类型C 是针对电缆直径大于等于12mm的测试,整个测试时间为20分钟。样品的前端固定。根据样品燃烧后的破坏长度来评估样品是否通过DIN EN 50266-2-4此项测试。
电线电缆其他标准:
EN 50266-1 common test methods for cables under fire conditions—Test for vertical flame spread of vertically-mounted bunched wired or cables-Part 1: apparatus. 着火条件下电缆的通用试验方法-多根成束垂直火焰燃烧-第1部分-设备装置
EN 50266-2-5 Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Small cables-Category D 着火条件下电缆的通用试验方法-多根成束垂直火焰燃烧-第2-5部分-小型电缆-类型D.
DIN EN 50266-2-4电线电缆多根成束垂直火焰燃烧(电缆直径≥12mm),需要进行此测试的电缆和导线(不包括数据线),燃烧测试后电缆的最大破坏长度不超过2.5m.
DIN EN 50305 section 9.1.1电线电缆多根成束垂直火焰燃烧(6mm<电缆直径<12mm) 需要进行此测试的电缆和导线(不包括数据线),燃烧测试后电缆的最大破坏长度不超过2.5m.
DIN EN 50305 section 9.1.2电线电缆多根成束垂直火焰燃烧(电缆直径≤6mm 需要进行此测试的电缆和导线(不包括数据线),燃烧测试后电缆的最大破坏长度不超过2.5m.
DIN EN 60332-1-2电线电缆单根垂直火焰燃烧,需要进行此测试的电缆和导线,包括数据线(光纤电缆、数据总线导线、同轴电缆),燃烧测试后,电缆的上端破坏长度不超过50mm,下端不超过540mm.
更多DIN EN 50266-2-4及DIN 5510-2电线电缆测试,请联系南京睿督公司
南京睿督联系方式:
电话:025-8658 3475 400-603-6575
网址:www.fire-test.com www.fire-test.cn
微信公众号:firetest 或 睿督防火测试
…