BS 476-4: Fire tests on building materials and structures- Part 4: Non-combustibility test for materials
BS 476-4: 建筑材料及结构的燃烧试验—第4部分:材料不燃性测试
BS 476-4不燃性测试方法
样品放入测试容器中,热电偶插入样品中心并且连接测试设备.此外样品的热电偶也放进炉子内(炉内温度达到750℃,这样的状态继续整个测试时间20分钟,在这个温度下记录下两个热电偶的相关数据材料的不燃性通过温升及燃烧时间来评估。
BS 476-4不燃性测试评定要求
温升(炉内的样品的中心温度上升) 必须小于50°C
整个测试中的出现火焰燃烧的时间必须小于10秒
BS 476 相关参考标准
BS 476: Fire tests on building materials and structures
BS 476-3:2004 external fire exposure roof test
BS 476-4:1970 Non-combustibility test for materials
BS 476-5:1979 Method of test of ignitability
BS476-6:1989+A1:2009 Method of test for propagation for materials
BS 476-7:1997 Surface spread of flame test for material
BS 476-11:1982 Method for assessing the heat emission from building materials
BS 476-12:1991 Ignitability of products by direct flame impingement
BS 476-15:1992 Method for measuring heat release of products-cone calorimeter
BS 476-20:1987 Method for determination of the fire resistance of elements of construction (general principles)
BS 476-21:1987 Methods for determination of the fire resistance of loadbearing elements of construction
BS 476-22:1987 Methods for determination of the fire resistance of non-loadbearing elements of construction
BS 476: 建筑材料及构件防火测试
BS 476-3:2004 室外屋顶的燃烧测试
BS 476-4:1970 材料不燃烧性测试
BS 476-5:1979 可燃性燃烧测试
BS476-6:1989 制品火势蔓延的试验方法
BS 476-7:1997制品表面火势蔓延的试验和分级方法
BS 476-11:1982建筑材料热辐射性能测试方法
BS 476-12:1991产品直接火焰冲击的可燃性测试方法
BS 476-15:1992产品放热性测试-锥形量热仪
BS 476-20:1987建筑构件耐火的测定方法(一般原理)
BS 476-21:1987 承重构件耐火的测定方法
BS 476-22:1987非承重建筑构件耐火性能测试方法
更多BS476-4不燃性测试及BS 476标准要求,请联系南京睿督公司
南京睿督联系方式:
电话:+86 25-8658 3475 +86 400-603-6575
网址:www.fire-test.com www.fire-test.cn
邮箱:info@fire-test.com
微信公众号:firetest 或 睿督防火测试
...